{"id":42024,"date":"2021-09-13T10:06:08","date_gmt":"2021-09-13T10:06:08","guid":{"rendered":"https:\/\/conduct.nl\/iec-60364-and-surge-protection-requirements-for-pv-installations\/"},"modified":"2025-10-16T16:51:43","modified_gmt":"2025-10-16T14:51:43","slug":"iec-60364-and-surge-protection-requirements-for-pv-installations","status":"publish","type":"post","link":"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/","title":{"rendered":"IEC 60364 et protection contre les surtensions PV"},"content":{"rendered":"<p>La s\u00e9curit\u00e9 est une priorit\u00e9 chez Conduct. Au cours de l\u2019ann\u00e9e \u00e9coul\u00e9e, nous avons particip\u00e9 activement \u00e0 divers projets o\u00f9 la protection contre l\u2019incendie et la foudre est essentielle. Il s\u2019agit notamment de tunnels, de centres de donn\u00e9es, de b\u00e2timents tertiaires et d\u2019installations photovolta\u00efques industrielles. Dans presque tous les segments du march\u00e9, la demande de s\u00e9curit\u00e9 structurelle ne cesse de cro\u00eetre. Selon le Rapport National sur les Tendances du Solaire, 55\u202f% du secteur de l\u2019\u00e9lectricit\u00e9 solaire se dit pr\u00e9occup\u00e9 par la s\u00e9curit\u00e9. Ce chiffre s\u2019\u00e9l\u00e8ve \u00e0 35\u202f% dans le secteur du solaire thermique. Une large majorit\u00e9 des r\u00e9pondants plaide pour des inspections obligatoires et un renforcement du contr\u00f4le des installations mises en service.<\/p>\n<p>&nbsp;<\/p>\n<p>Le respect des normes en vigueur, telles que la NEN 1010:2020 avec l\u2019addendum C1:2024, y joue un r\u00f4le central. Cette norme est largement appliqu\u00e9e comme interpr\u00e9tation des exigences de s\u00e9curit\u00e9 du Bouwbesluit 2012 (r\u00e8glement de construction n\u00e9erlandais). Avec RoofSupport, nous garantissons un acheminement des c\u00e2bles s\u00e9curis\u00e9 et conforme aux normes. En combinaison avec RoofSupport PVbox, nous assurons \u00e9galement le raccordement correct de l\u2019installation ainsi que sa protection, notamment par des dispositifs de protection contre les surtensions et des interrupteurs de pompier SALTEK. Ces applications s\u2019inscrivent parfaitement dans l\u2019une de nos valeurs fondamentales\u202f: la s\u00e9curit\u00e9. C\u2019est pourquoi nous d\u00e9veloppons activement notre gamme avec des solutions de s\u00e9curit\u00e9 \u00e9lectrique et incendie. Nos PVshelter int\u00e8grent \u00e9galement des dispositifs de s\u00e9curit\u00e9 \u00e0 l\u2019\u00e9chelle du syst\u00e8me. Cela confirme notre vision\u202f: la s\u00e9curit\u00e9 est un facteur d\u00e9terminant dans l\u2019application des exigences normatives et des inspections Scope 12.<\/p>\n<p>&nbsp;<\/p>\n<p><strong>NEN 1010:2020 + C1:2024 et protection contre les surtensions<\/strong><br \/>\nQuelques articles essentiels de la norme :<\/p>\n<ul>\n<li>131.6 \u2013 Protection contre les perturbations de tension et les influences \u00e9lectromagn\u00e9tiques<\/li>\n<li>131.6.1 Les personnes, les animaux et les biens doivent \u00eatre prot\u00e9g\u00e9s contre les risques de blessures ou d&#8217;effets nocifs r\u00e9sultant de d\u00e9fauts entre des circuits \u00e9lectriques de niveaux de tension diff\u00e9rents.<\/li>\n<li>131.6.2 Les personnes, les animaux et les biens doivent \u00eatre prot\u00e9g\u00e9s contre les dommages dus \u00e0 des surtensions, par exemple caus\u00e9es par des d\u00e9charges atmosph\u00e9riques ou des op\u00e9rations de commutation.<\/li>\n<\/ul>\n<p>Remarque\u202f: pour la protection contre la foudre directe, se r\u00e9f\u00e9rer \u00e0 la s\u00e9rie NEN-EN-IEC 62305.<\/p>\n<p>&nbsp;<\/p>\n<p><strong>443.1 \u2013 G\u00e9n\u00e9ralit\u00e9s<\/strong><br \/>\nLe dimensionnement de l\u2019installation doit tenir compte des surtensions susceptibles de survenir \u00e0 l\u2019entr\u00e9e de l\u2019installation, en fonction du niveau local de foudroiement et des caract\u00e9ristiques des parafoudres (SPD) utilis\u00e9s. L\u2019objectif est de limiter les effets des surtensions \u00e0 un niveau acceptable pour la s\u00e9curit\u00e9 des personnes et la continuit\u00e9 d\u2019exploitation.<\/p>\n<p>&nbsp;<\/p>\n<p><strong>712.443.101 \u2013 Protection contre les surtensions transitoires<\/strong><br \/>\nLorsque la section 443 impose une protection contre les surtensions, celle-ci doit \u00e9galement \u00eatre appliqu\u00e9e du c\u00f4t\u00e9 DC de l\u2019installation photovolta\u00efque.<\/p>\n<p>Plus d\u2019informations sur l\u2019application de la protection contre les surtensions dans les installations photovolta\u00efques sont disponibles sur le site Scope 12 Inspecties.<\/p>\n<p>&nbsp;<\/p>\n","protected":false},"excerpt":{"rendered":"<p>La s\u00e9curit\u00e9 est une priorit\u00e9 chez Conduct. Au cours de l\u2019ann\u00e9e \u00e9coul\u00e9e, nous avons particip\u00e9 activement \u00e0 divers projets o\u00f9 la protection contre l\u2019incendie et la foudre est essentielle. Il s\u2019agit notamment de tunnels, de centres de donn\u00e9es, de b\u00e2timents tertiaires et d\u2019installations photovolta\u00efques industrielles. Dans presque tous les segments du march\u00e9, la demande de &hellip;<\/p>\n","protected":false},"author":7,"featured_media":46942,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[2160],"tags":[],"class_list":["post-42024","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-bliksem-en-overspanningsbeveiliging-fr"],"acf":[],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v26.9 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>Surge Protection in PV Installations \u2013 IEC 60364 Compliance<\/title>\n<meta name=\"description\" content=\"D\u00e9couvrez comment Conduct int\u00e8gre la protection contre les surtensions et la s\u00e9curit\u00e9 dans les installations photovolta\u00efques selon la norme IEC 60364 et \u00e0 l\u2019aide de composants SPD.\" \/>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/\" \/>\n<meta property=\"og:locale\" content=\"fr_FR\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"Surge Protection in PV Installations \u2013 IEC 60364 Compliance\" \/>\n<meta property=\"og:description\" content=\"D\u00e9couvrez comment Conduct int\u00e8gre la protection contre les surtensions et la s\u00e9curit\u00e9 dans les installations photovolta\u00efques selon la norme IEC 60364 et \u00e0 l\u2019aide de composants SPD.\" \/>\n<meta property=\"og:url\" content=\"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/\" \/>\n<meta property=\"og:site_name\" content=\"Conduct\" \/>\n<meta property=\"article:published_time\" content=\"2021-09-13T10:06:08+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2025-10-16T14:51:43+00:00\" \/>\n<meta property=\"og:image\" content=\"https:\/\/conduct.nl\/app\/uploads\/2021\/09\/michael-pointner-1I5h9qmJ7DQ-unsplash-scaled-e1760606598867.jpg\" \/>\n\t<meta property=\"og:image:width\" content=\"2560\" \/>\n\t<meta property=\"og:image:height\" content=\"1707\" \/>\n\t<meta property=\"og:image:type\" content=\"image\/jpeg\" \/>\n<meta name=\"author\" content=\"Ricardo\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"Ricardo\" \/>\n\t<meta name=\"twitter:label2\" content=\"Est. reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"3 minutes\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\/\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/#article\",\"isPartOf\":{\"@id\":\"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/\"},\"author\":{\"name\":\"Ricardo\",\"@id\":\"https:\/\/conduct.nl\/#\/schema\/person\/60ebffdd7bf2f7257cf22cd582bbf9b8\"},\"headline\":\"IEC 60364 et protection contre les surtensions PV\",\"datePublished\":\"2021-09-13T10:06:08+00:00\",\"dateModified\":\"2025-10-16T14:51:43+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/\"},\"wordCount\":525,\"image\":{\"@id\":\"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/#primaryimage\"},\"thumbnailUrl\":\"https:\/\/conduct.nl\/app\/uploads\/2021\/09\/michael-pointner-1I5h9qmJ7DQ-unsplash-scaled-e1760606598867.jpg\",\"articleSection\":[\"Protection contre la foudre et les surtensions\"],\"inLanguage\":\"fr-FR\"},{\"@type\":\"WebPage\",\"@id\":\"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/\",\"url\":\"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/\",\"name\":\"Surge Protection in PV Installations \u2013 IEC 60364 Compliance\",\"isPartOf\":{\"@id\":\"https:\/\/conduct.nl\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/#primaryimage\"},\"image\":{\"@id\":\"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/#primaryimage\"},\"thumbnailUrl\":\"https:\/\/conduct.nl\/app\/uploads\/2021\/09\/michael-pointner-1I5h9qmJ7DQ-unsplash-scaled-e1760606598867.jpg\",\"datePublished\":\"2021-09-13T10:06:08+00:00\",\"dateModified\":\"2025-10-16T14:51:43+00:00\",\"author\":{\"@id\":\"https:\/\/conduct.nl\/#\/schema\/person\/60ebffdd7bf2f7257cf22cd582bbf9b8\"},\"description\":\"D\u00e9couvrez comment Conduct int\u00e8gre la protection contre les surtensions et la s\u00e9curit\u00e9 dans les installations photovolta\u00efques selon la norme IEC 60364 et \u00e0 l\u2019aide de composants SPD.\",\"breadcrumb\":{\"@id\":\"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/#breadcrumb\"},\"inLanguage\":\"fr-FR\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"fr-FR\",\"@id\":\"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/#primaryimage\",\"url\":\"https:\/\/conduct.nl\/app\/uploads\/2021\/09\/michael-pointner-1I5h9qmJ7DQ-unsplash-scaled-e1760606598867.jpg\",\"contentUrl\":\"https:\/\/conduct.nl\/app\/uploads\/2021\/09\/michael-pointner-1I5h9qmJ7DQ-unsplash-scaled-e1760606598867.jpg\",\"width\":2560,\"height\":1707},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\/\/conduct.nl\/fr\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"IEC 60364 et protection contre les surtensions PV\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\/\/conduct.nl\/#website\",\"url\":\"https:\/\/conduct.nl\/\",\"name\":\"Conduct\",\"description\":\"Conduct Technical Solutions\",\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\/\/conduct.nl\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"fr-FR\"},{\"@type\":\"Person\",\"@id\":\"https:\/\/conduct.nl\/#\/schema\/person\/60ebffdd7bf2f7257cf22cd582bbf9b8\",\"name\":\"Ricardo\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"fr-FR\",\"@id\":\"https:\/\/conduct.nl\/#\/schema\/person\/image\/\",\"url\":\"https:\/\/secure.gravatar.com\/avatar\/1bc40502937d556b6349b78444c696078ca24bd7e391c2d9a22ed13f303b4bf1?s=96&d=mm&r=g\",\"contentUrl\":\"https:\/\/secure.gravatar.com\/avatar\/1bc40502937d556b6349b78444c696078ca24bd7e391c2d9a22ed13f303b4bf1?s=96&d=mm&r=g\",\"caption\":\"Ricardo\"},\"url\":\"https:\/\/conduct.nl\/fr\/author\/1627045716452\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"Surge Protection in PV Installations \u2013 IEC 60364 Compliance","description":"D\u00e9couvrez comment Conduct int\u00e8gre la protection contre les surtensions et la s\u00e9curit\u00e9 dans les installations photovolta\u00efques selon la norme IEC 60364 et \u00e0 l\u2019aide de composants SPD.","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/","og_locale":"fr_FR","og_type":"article","og_title":"Surge Protection in PV Installations \u2013 IEC 60364 Compliance","og_description":"D\u00e9couvrez comment Conduct int\u00e8gre la protection contre les surtensions et la s\u00e9curit\u00e9 dans les installations photovolta\u00efques selon la norme IEC 60364 et \u00e0 l\u2019aide de composants SPD.","og_url":"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/","og_site_name":"Conduct","article_published_time":"2021-09-13T10:06:08+00:00","article_modified_time":"2025-10-16T14:51:43+00:00","og_image":[{"width":2560,"height":1707,"url":"https:\/\/conduct.nl\/app\/uploads\/2021\/09\/michael-pointner-1I5h9qmJ7DQ-unsplash-scaled-e1760606598867.jpg","type":"image\/jpeg"}],"author":"Ricardo","twitter_card":"summary_large_image","twitter_misc":{"Written by":"Ricardo","Est. reading time":"3 minutes"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/#article","isPartOf":{"@id":"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/"},"author":{"name":"Ricardo","@id":"https:\/\/conduct.nl\/#\/schema\/person\/60ebffdd7bf2f7257cf22cd582bbf9b8"},"headline":"IEC 60364 et protection contre les surtensions PV","datePublished":"2021-09-13T10:06:08+00:00","dateModified":"2025-10-16T14:51:43+00:00","mainEntityOfPage":{"@id":"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/"},"wordCount":525,"image":{"@id":"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/#primaryimage"},"thumbnailUrl":"https:\/\/conduct.nl\/app\/uploads\/2021\/09\/michael-pointner-1I5h9qmJ7DQ-unsplash-scaled-e1760606598867.jpg","articleSection":["Protection contre la foudre et les surtensions"],"inLanguage":"fr-FR"},{"@type":"WebPage","@id":"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/","url":"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/","name":"Surge Protection in PV Installations \u2013 IEC 60364 Compliance","isPartOf":{"@id":"https:\/\/conduct.nl\/#website"},"primaryImageOfPage":{"@id":"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/#primaryimage"},"image":{"@id":"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/#primaryimage"},"thumbnailUrl":"https:\/\/conduct.nl\/app\/uploads\/2021\/09\/michael-pointner-1I5h9qmJ7DQ-unsplash-scaled-e1760606598867.jpg","datePublished":"2021-09-13T10:06:08+00:00","dateModified":"2025-10-16T14:51:43+00:00","author":{"@id":"https:\/\/conduct.nl\/#\/schema\/person\/60ebffdd7bf2f7257cf22cd582bbf9b8"},"description":"D\u00e9couvrez comment Conduct int\u00e8gre la protection contre les surtensions et la s\u00e9curit\u00e9 dans les installations photovolta\u00efques selon la norme IEC 60364 et \u00e0 l\u2019aide de composants SPD.","breadcrumb":{"@id":"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/#breadcrumb"},"inLanguage":"fr-FR","potentialAction":[{"@type":"ReadAction","target":["https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/"]}]},{"@type":"ImageObject","inLanguage":"fr-FR","@id":"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/#primaryimage","url":"https:\/\/conduct.nl\/app\/uploads\/2021\/09\/michael-pointner-1I5h9qmJ7DQ-unsplash-scaled-e1760606598867.jpg","contentUrl":"https:\/\/conduct.nl\/app\/uploads\/2021\/09\/michael-pointner-1I5h9qmJ7DQ-unsplash-scaled-e1760606598867.jpg","width":2560,"height":1707},{"@type":"BreadcrumbList","@id":"https:\/\/conduct.nl\/fr\/iec-60364-and-surge-protection-requirements-for-pv-installations\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/conduct.nl\/fr\/"},{"@type":"ListItem","position":2,"name":"IEC 60364 et protection contre les surtensions PV"}]},{"@type":"WebSite","@id":"https:\/\/conduct.nl\/#website","url":"https:\/\/conduct.nl\/","name":"Conduct","description":"Conduct Technical Solutions","potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/conduct.nl\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"fr-FR"},{"@type":"Person","@id":"https:\/\/conduct.nl\/#\/schema\/person\/60ebffdd7bf2f7257cf22cd582bbf9b8","name":"Ricardo","image":{"@type":"ImageObject","inLanguage":"fr-FR","@id":"https:\/\/conduct.nl\/#\/schema\/person\/image\/","url":"https:\/\/secure.gravatar.com\/avatar\/1bc40502937d556b6349b78444c696078ca24bd7e391c2d9a22ed13f303b4bf1?s=96&d=mm&r=g","contentUrl":"https:\/\/secure.gravatar.com\/avatar\/1bc40502937d556b6349b78444c696078ca24bd7e391c2d9a22ed13f303b4bf1?s=96&d=mm&r=g","caption":"Ricardo"},"url":"https:\/\/conduct.nl\/fr\/author\/1627045716452\/"}]}},"_links":{"self":[{"href":"https:\/\/conduct.nl\/fr\/wp-json\/wp\/v2\/posts\/42024","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/conduct.nl\/fr\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/conduct.nl\/fr\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/conduct.nl\/fr\/wp-json\/wp\/v2\/users\/7"}],"replies":[{"embeddable":true,"href":"https:\/\/conduct.nl\/fr\/wp-json\/wp\/v2\/comments?post=42024"}],"version-history":[{"count":7,"href":"https:\/\/conduct.nl\/fr\/wp-json\/wp\/v2\/posts\/42024\/revisions"}],"predecessor-version":[{"id":47096,"href":"https:\/\/conduct.nl\/fr\/wp-json\/wp\/v2\/posts\/42024\/revisions\/47096"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/conduct.nl\/fr\/wp-json\/wp\/v2\/media\/46942"}],"wp:attachment":[{"href":"https:\/\/conduct.nl\/fr\/wp-json\/wp\/v2\/media?parent=42024"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/conduct.nl\/fr\/wp-json\/wp\/v2\/categories?post=42024"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/conduct.nl\/fr\/wp-json\/wp\/v2\/tags?post=42024"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}